ups role: NUT server on home.debyl.io for the CyberPower PR1500RT2U that backs
both it and truenas.localdomain, with staged shutdown (TrueNAS sheds at t+2min,
host at 10% charge) and best-effort IPMI power-on when mains returns. The 10%
threshold leans on ignorelb + override.battery.charge.low rather than a custom
poller, because CyberPower asserts its own low-battery flag far too early.
Credentials come from vault vars; nothing sensitive is templated in the clear.

Nextcloud background jobs: both instances have backgroundjobs_mode "cron", which
expects an external caller every ~5 minutes, and nothing was calling. The
personal instance had not run a background job since 2026-05-14 and skudak since
2024-11-20. Consequently trash and file versions never expired, stale chunked
uploads accumulated, calendar reminders never fired, and nextcloud.log was never
rotated -- which quietly made the existing log_rotate_size cap inert. Added a
systemd timer per instance, skipping cleanly when the container is down or in
maintenance so deploy windows don't show up as failed units.

Trash retention on the personal instance: the default "auto" only expires when
disk space demands it, so 66 GB of >30-day deletions sat on a host with 1.3 TB
free -- effectively unbounded. "auto, 30" makes the 30-day expiry unconditional
while still purging early under pressure.

Image bumps:
  nextcloud       33.0.0  -> 34.0.2   (both cloud and skudak-cloud)
  greg-time-bot   3.9.25  -> 3.10.0
  fulfillr        20260723.2044 -> 20260728.2155  (prod and dev)

The fulfillr bump records what is already deployed: both containers were rolled
to that image on 2026-07-29 for SCRUM-156 (digital product releases + customer
update campaign). Committing it keeps the repo from claiming an older tag than
the host is actually running, which would otherwise roll fulfillr backwards on
the next clean-checkout deploy.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
2026-07-30 13:00:51 -04:00

115 lines
4.6 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# ups
UPS monitoring and staged shutdown for the home rack.
A CyberPower PR1500RT2U (`0764:0601`) is cabled by USB to `home.debyl.io` and
backs both that host and `truenas.localdomain` (Dell PowerEdge R415). This role
makes `home.debyl.io` the NUT server and gives it the ability to power TrueNAS
back on over IPMI.
## Outage sequence
| When | What happens | Driven by |
| --- | --- | --- |
| t+0 | UPS goes on battery, `ONBATT` logged to journald → Graylog | `upsmon` |
| t+2min | TrueNAS shuts itself down cleanly, shedding ~200 W | TrueNAS UPS service, Slave mode, `Shutdown Timer 120` |
| 10% charge | `home.debyl.io` shuts itself down and tells the UPS to cut its output | `upsmon` `SHUTDOWNCMD` + `/lib/systemd/system-shutdown/nutshutdown` |
| mains returns | UPS re-energizes; both machines power themselves back up | R415 `always-on` restore policy; `home.debyl.io` BIOS *After Power Loss → Power On* |
| mains back +5min | Best-effort IPMI power-on, if a dedicated iDRAC is ever fitted | `upssched``ups-restore.sh` |
| host boot | Same restore check, for the deep-drain case | `ups-restore.service` |
The 10% threshold is not a custom poller. CyberPower asserts its own low-battery
flag around 2035%, so `ups.conf` sets `ignorelb` plus
`override.battery.charge.low`, and stock `upsmon` fires at exactly the
configured percentage.
Likewise, the 2-minute TrueNAS shed is TrueNAS's own native "shutdown timer"
setting — no SSH key and no shutdown script from this side.
## Powering TrueNAS back on
Neither Wake-on-LAN nor IPMI works on this box today, so restore is done with
the chassis power restore policy instead.
**Wake-on-LAN is out.** `bce0` advertises no WOL capability (`ifconfig -m bce0`
has no `WOL_MAGIC`) and both NICs are bonded into an LACP `lagg0`.
**IPMI is out too, for now.** The iDRAC is in `shared / LOM1` mode and the
Enterprise card that would provide a dedicated management port is not fitted:
```
$ ipmitool sdr elist | grep -i idrac
iDRAC6 Ent Pres | 70h | ok | 7.1 | Absent
```
A shared-LOM iDRAC6 Express has no standby power. Measured directly: with the
chassis powered off the BMC does not even answer ARP, and it only reappears
~200s into POST, at the moment the host brings the NIC link up. That is a
hardware limitation, not a switch or BIOS problem.
**So restore works like this instead.** `ipmitool chassis policy always-on` is
set on the R415. On a deep outage `home.debyl.io` halts at 10% and NUT's
shutdown hook tells the UPS to cut its output; when mains returns the UPS
re-energizes, the R415 sees AC and boots itself.
The gap is the medium outage — mains returns after TrueNAS has shed but before
the battery reaches 10%. The UPS never cuts power, so TrueNAS stays off and
needs a manual power button press. Fitting a used iDRAC6 Enterprise card and
running `ipmitool delloem lan set dedicated` (plus a cable to the dedicated
port) closes that gap, and `ups-restore.sh` starts working with no code
changes — it is already deployed and simply logs and exits while the BMC is
unreachable.
## One-time setup outside Ansible
These are not managed by this role.
**iDRAC (already done, via `ipmitool` on TrueNAS):**
```
ipmitool lan set 1 ipsrc static
ipmitool lan set 1 ipaddr 192.168.1.12
ipmitool lan set 1 netmask 255.255.255.0
ipmitool lan set 1 defgw ipaddr 192.168.1.1
ipmitool lan set 1 access on # was disabled - nothing answers without this
ipmitool channel setaccess 1 2 callin=on ipmi=on link=on privilege=4
ipmitool user set password 2 '<idrac_password>'
ipmitool chassis policy always-on # this is what restores power after an outage
```
`idrac_password` is also the iDRAC web UI password for `root` - they share a
user database.
**TrueNAS UI → Services → UPS** (enable + start automatically):
| Field | Value |
| --- | --- |
| UPS Mode | Slave |
| Remote Host | `192.168.1.10` |
| Remote Port | `3493` |
| Identifier | `cyberpower` |
| Monitor User | `truenas` |
| Monitor Password | vault `nut_truenas_password` |
| Shutdown Mode | UPS goes on battery |
| Shutdown Timer | `120` |
| Shutdown Command | `/sbin/shutdown -p now` |
| Power Off UPS | unchecked |
**BIOS on `home.debyl.io`** (Lenovo 10MR0004US): Power → *After Power Loss*
**Power On**. On a full drain the NUT shutdown hook
(`/lib/systemd/system-shutdown/nutshutdown`) tells the UPS to cut its own
output; this BIOS setting is what brings the host back when mains returns.
## Vault keys
`nut_upsmon_password`, `nut_truenas_password`, `idrac_password`
## Operating
```
upsc cyberpower # full UPS status
upsc cyberpower battery.charge
sudo /usr/local/bin/truenas-power.sh status|on|soft|off
journalctl -t ups-restore -t ups-sched
```