Bastian de Byl 5776dbe1bf UPS monitoring, Nextcloud cron, container image bumps
ups role: NUT server on home.debyl.io for the CyberPower PR1500RT2U that backs
both it and truenas.localdomain, with staged shutdown (TrueNAS sheds at t+2min,
host at 10% charge) and best-effort IPMI power-on when mains returns. The 10%
threshold leans on ignorelb + override.battery.charge.low rather than a custom
poller, because CyberPower asserts its own low-battery flag far too early.
Credentials come from vault vars; nothing sensitive is templated in the clear.

Nextcloud background jobs: both instances have backgroundjobs_mode "cron", which
expects an external caller every ~5 minutes, and nothing was calling. The
personal instance had not run a background job since 2026-05-14 and skudak since
2024-11-20. Consequently trash and file versions never expired, stale chunked
uploads accumulated, calendar reminders never fired, and nextcloud.log was never
rotated -- which quietly made the existing log_rotate_size cap inert. Added a
systemd timer per instance, skipping cleanly when the container is down or in
maintenance so deploy windows don't show up as failed units.

Trash retention on the personal instance: the default "auto" only expires when
disk space demands it, so 66 GB of >30-day deletions sat on a host with 1.3 TB
free -- effectively unbounded. "auto, 30" makes the 30-day expiry unconditional
while still purging early under pressure.

Image bumps:
  nextcloud       33.0.0  -> 34.0.2   (both cloud and skudak-cloud)
  greg-time-bot   3.9.25  -> 3.10.0
  fulfillr        20260723.2044 -> 20260728.2155  (prod and dev)

The fulfillr bump records what is already deployed: both containers were rolled
to that image on 2026-07-29 for SCRUM-156 (digital product releases + customer
update campaign). Committing it keeps the repo from claiming an older tag than
the host is actually running, which would otherwise roll fulfillr backwards on
the next clean-checkout deploy.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
2026-07-30 13:00:51 -04:00

19 lines
739 B
Django/Jinja

# {{ ansible_managed }}
[{{ ups_name }}]
driver = usbhid-ups
port = auto
vendorid = {{ ups_vendorid }}
productid = {{ ups_productid }}
desc = "{{ ups_desc }}"
# CyberPower asserts its own low-battery flag around 20-35%, far too
# early for us. Ignore it and derive LB from our own threshold so
# upsmon fires SHUTDOWNCMD at exactly {{ ups_low_charge_pct }}%.
ignorelb
override.battery.charge.low = {{ ups_low_charge_pct }}
# Unlock driver.killpower. Without this the driver refuses to cut UPS
# output at shutdown, and the R415's always-on power restore policy
# would never see AC drop and return - i.e. nothing comes back after a
# deep outage. See README.md.
allow_killpower