5776dbe1bf
ups role: NUT server on home.debyl.io for the CyberPower PR1500RT2U that backs both it and truenas.localdomain, with staged shutdown (TrueNAS sheds at t+2min, host at 10% charge) and best-effort IPMI power-on when mains returns. The 10% threshold leans on ignorelb + override.battery.charge.low rather than a custom poller, because CyberPower asserts its own low-battery flag far too early. Credentials come from vault vars; nothing sensitive is templated in the clear. Nextcloud background jobs: both instances have backgroundjobs_mode "cron", which expects an external caller every ~5 minutes, and nothing was calling. The personal instance had not run a background job since 2026-05-14 and skudak since 2024-11-20. Consequently trash and file versions never expired, stale chunked uploads accumulated, calendar reminders never fired, and nextcloud.log was never rotated -- which quietly made the existing log_rotate_size cap inert. Added a systemd timer per instance, skipping cleanly when the container is down or in maintenance so deploy windows don't show up as failed units. Trash retention on the personal instance: the default "auto" only expires when disk space demands it, so 66 GB of >30-day deletions sat on a host with 1.3 TB free -- effectively unbounded. "auto, 30" makes the 30-day expiry unconditional while still purging early under pressure. Image bumps: nextcloud 33.0.0 -> 34.0.2 (both cloud and skudak-cloud) greg-time-bot 3.9.25 -> 3.10.0 fulfillr 20260723.2044 -> 20260728.2155 (prod and dev) The fulfillr bump records what is already deployed: both containers were rolled to that image on 2026-07-29 for SCRUM-156 (digital product releases + customer update campaign). Committing it keeps the repo from claiming an older tag than the host is actually running, which would otherwise roll fulfillr backwards on the next clean-checkout deploy. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
19 lines
739 B
Django/Jinja
19 lines
739 B
Django/Jinja
# {{ ansible_managed }}
|
|
|
|
[{{ ups_name }}]
|
|
driver = usbhid-ups
|
|
port = auto
|
|
vendorid = {{ ups_vendorid }}
|
|
productid = {{ ups_productid }}
|
|
desc = "{{ ups_desc }}"
|
|
# CyberPower asserts its own low-battery flag around 20-35%, far too
|
|
# early for us. Ignore it and derive LB from our own threshold so
|
|
# upsmon fires SHUTDOWNCMD at exactly {{ ups_low_charge_pct }}%.
|
|
ignorelb
|
|
override.battery.charge.low = {{ ups_low_charge_pct }}
|
|
# Unlock driver.killpower. Without this the driver refuses to cut UPS
|
|
# output at shutdown, and the R415's always-on power restore policy
|
|
# would never see AC drop and return - i.e. nothing comes back after a
|
|
# deep outage. See README.md.
|
|
allow_killpower
|